Ex-eac-logo Eac-logo Iecex-approval Atex-approval Ce-approval Inmetro-approval Gost-approval
1-21-090

BExBG21 Explosion Proof Xenon Beacon 21 Joule

The flameproof BExBG21 Xenon beacons are suitable for Zone 1, 2, 21 & 22 applications. Approved to IECEx, ATEX, Ex EAC and INMETRO standards.

The BExBG21 21 Joule beacons robust construction enables installation in the harshest of environments. The BExBG21 has three distinct user selectable flash patterns and for units with DC operating voltages a second stage flash pattern can be selected remotely. Additional features include a stainless steel guard and stainless steel mounting bracket as standard. 
The BEx range features enclosures manufactured from corrosion proof, marine grade copper free LM6 aluminium with a chromate and powder coat finish. All models have two M20 cable entries, large termination areas containing in & out terminals and an ingress protection of IP66/67.

Specification

 
Energy: 21 Joules
Flash rate: 1Hz, 2Hz & double strike 1Hz
Peak Candela: 2,100,000 cd - calculated from energy (J)
Effective Intensity cd: 1,050 cd - calculated from energy (J)
Peak Candela: 118,537 cd* - measured ref. to I.E.S.
Effective Intensity cd: 520 cd* - measured ref. to I.E.S.
Lens colours: Amber, Blue, Clear, Green, Magenta, Red & Yellow
Voltages DC: 24vdc; 48vdc
Voltages AC: 115vac; 230vac
Ingress protection: IP66/67
Enclosure matl: Marine grade copper free LM6 Aluminium
Enclosure finish: Chromate & powder coated finish - anti-corrosion.
Colour: RAL3000 Red (others available on request)
Cable entries: Dual M20 ISO (one stopping plug inc)
Terminals: 0.5 - 2.5mm² (20-14 AWG)
Enclosure volume: <2 litres
Line monitoring: Blocking diode included
EOL Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor
or diode (DC versions) can be added
Grounding stud: M5
Temperature range: -50° to +70°C (-58°F to +158°F)
Relative humidity: 90% at 20°C [68°F]
Tube life: Emissions are reduced to 70% after 5 million flashes
Weight: DC: 2.65kg/5.83Ibs AC: 2.95kg/6.49Ibs
*All candela data is representative of performance with clear lens at optimum voltage.

Current Consumption

Version: Voltage: Current:
24V dc 20-28V dc 1.2A
48V dc 42-54V dc 600mA
115V ac 50/60Hz +/-10% 560mA
230V ac 50/60Hz +/-10% 280mA

Part Codes

Version: Part code:
Product type: BExBG21 Explosion proof 21J Xenon Beacon
Type: DP Ex d, UV stable PC Colour Lens
Voltage: DC024
DC048
AC115
AC230
24V dc
48V dc
115V ac
240V ac
Cable Entry Type:[e]






Note:
A
B
C
D
E
F
G
2 x M20x1.5mm
2 x 1/2" NPT - adaptors
2 x 3/4" NPT - adaptors
2 x M25x1.5mm - adaptors
1 x 1/2" NPT - adaptor
1 x 3/4" NPT - adaptor
1 x M25x1.5mm - adaptor
M20 stopping plugs for unused entries supplied
Adaptor/Stopping
plug material: [m]
B
N
S
Brass
Nickel Plated
Stainless Steel
Bracket/guard matl: [s] 1
2
3
4
A2 304 Stainless Steel
A4 316 Stainless Steel
A2 304 St/St with Equip. Tag
A4 316 St/St with Equip. Tag (304)
Product version: [v] A1 Default - IECEx, ATEX, Ex EAC & INMETRO
Enclosure colour: [x] R
S
Red RAL3000
Special - contact E2S
Lens colour: [y] A
B
Amber
Blue
C
G
Clear
Green
M
R
Magenta
Red
Y Yellow

Flash Patterns

Pattern: Type: Stg 2 (DC)
SF 1Hz (60fpm) Both Xenon tubes flash together AF
AF 2Hz (120fpm) Xenon tubes flash alternately SF
DF 1Hz (60fpm) Double strike flash SF

Assemblies

Assemblies: The products from the BEx range are available as multiple unit assemblies pre-wired with and without junction boxes. See the BExP data sheet for further info or contact E2S sales.

Coding

  • II 2G Ex d IIC T3 Gb Ta. -50°C to +70°C
  • II 2D Ex tb IIIC T150°C Db Ta. -50°C to +40°C
  • II 2D Ex tb IIIC T165°C Db Ta. -50°C to +55°C
  • II 2D Ex tb IIIC T180°C Db Ta. -50°C to +70°C

Effective Candela lens colour factor

 
Amber Blue Clear Green Red Yellow
0.70 0.24 1.00 0.25 0.23 0.93