1-34-040
D2xC2LD2-H Horn & LED Synchronized UL464 & UL1971
The haz loc D2xC2LD2-H is an auto-synchronizing alarm horn & LED light/beacon tested to UL464 & UL1971 suitable for public mode fire alarm, ADA compliant, hearing impaired applications. The unit is UL/cUL approved for Class I Div 2, Class II Div 2, Class I Zone 2/22 as well as IECEx and ATEX certified for Zone 2 and 22 hazardous area applications.
The D2xC2LD2-H utilises an array of high power Cree® LED's, orientated to optimise visibility in any direction. Multiple D2xC2LD2-H units will auto-synchronize when powered from the same power source removing the need for any additonal sync modules on the circuit. The horn & LED light can be powered from the same source, simplifying installation and reducing cabling costs. UL1971 effective candela rating of 38.38cd.
Specification
Alarm Horn Sounder: | ||
Maximum output: | 116dB(A) @ 1 metre [107dB(A) @ 10ft/3m] | |
Nominal output: | 112dB(A) @ 1m +/- 3dB - Tone 2 [103dB(A) @ 10ft/3m] | |
No. of tones: | 64 (UKOOA / PFEER compliant) | |
No. of stages: | 4 | |
Volume control: | Adjustable -12dB(A) [Tone 2] | |
Effective range: | 125m/410ft @ 1KHz | |
Synchronization | All alarm tones synchronize | |
LED Beacon/Light: | ||
Source: | Array of 4 x High Power Cree® LED's | |
Modes: | 1Hz flash (60 fpm) 1.3Hz flash (80 fpm) 2Hz flash (120 fpm |
|
Eff. Intensity cd: | 38.38 cd UL1971 Public mode fire | |
Eff. Intensity cd: | 180 cd UL1638 General signaling | |
Peak Intensity cd: | 300,000 cd | |
LED life: | >60,000 hours | |
Synchronization: | Flash rates synchronize for a minimum of 2 hours per UL1971 | |
General: | ||
Voltage: | 24V dc [16-33V dc] | |
In rush: | 2.1A for <10ms | |
Ingress protection: | IP rating per EN60529:IP66 Type rating per UL50E/NEMA250:4/4X/3R/13 |
|
Enclosure material: | Marine grade LM6 aluminum alloy | |
Enclosure colour: | Red (RAL3000) | |
Lens material: | Borosilicate glass | |
Cable entries: | 2 x 1/2"NPT | |
Stopping plugs: | Nickel Plated Brass plugs included | |
Ground/Earth stud: | M5 | |
Terminals: | 0.5 - 2.5mm² (20-14 AWG) | |
Line monitoring: | Blocking diode included EOL can be factory fitted |
|
Operating temp: | -40 to +50°C [-40° to +122°F] | |
Storage temp: | -40 to +70°C [-40° to +158°F] | |
Relative humidity: | 95% | |
Weight: | 4.00kg/8.82Ibs |
Current Consumption
Nominal Voltage: |
Voltage range: |
Flash Rate setting: |
Nominal current [Beacon]: |
Nominal current [Alarm Horn]: |
---|---|---|---|---|
24V dc |
Regulated 16-33V dc |
1Hz (60fpm) 1.3Hz (80 fpm) 2Hz (120fpm) |
99.5mA 104mA 103mA |
313mA |
Part Codes
Part Code: | Ident.: | Description: | |
---|---|---|---|
Product type: | D2xC2LD2 | Combination Alarm Horn & LED Beacon/Light | |
Voltage: | DC024 | 24V dc (16-33Vdc) | |
Cable entries: [e] | B | 2 x 1/2” NPT | |
Stopping plug material: [m] | N | Nickel plated brass | |
Lens Guard: [s] | 0 | No lens Guard | |
Version: [v] | H1 | UL, cUL, IECEx & ATEX - UL1971 | |
Enclosure: [x] | R | Red RAL3000 | |
Lens colour: [y] | C | Clear | |
e.g: D2xC2LD2DC024BN0H1R/C | D2xC2LD2-H LED Beacon, 24Vdc nickel plated brass stopping plugs, UL, cUL, IECEx & ATEX approved - UL1971 Red enclosure with Clear lens |
||
Also available as the D2xB1LD2-H LED standalone beacon see www.e2s.com/1-31-060 |
Coding
- NEC / CEC: Class I Div 2 ABCD T2B Ta -40°C to +70°C
Class I Div 2 ABCD T4 Ta -40°C to +50°C
Class I Div 2 ABCD T4A Ta -40°C to +40°C
Class II Div 2 EFG T6 Ta -40°C to +50°C
Class III Div 1&2 Ta -40°C to +50°C - NEC: Class I Zone 2 AEx nA IIC T4 Gc (Ta -40°C to +50°C)
AEx tc IIIC 75°C Dc Ta -40°C to +50°C - CEC: Class I Zone 2 Ex nA IIC Gc T4 Ta -40°C to +50°C
Zone 22 Ex tc IIIC 75°C Dc Ta -20°C to +55°C - IECEx & ATEX: II 3G Ex nA IIC T4 Gc Ta -40°C to +50°C
II 3D Ex tc IIIC 75°C Dc Ta -40°C to +50°C
Multi-function patterns
Stage 1: [On board] |
Stage 2: [Remote] |
Stage 3: [Remote] |
|
---|---|---|---|
Steady High Power | Flashing 1Hz † | Triple Strike | |
Steady Low Power | Flashing 1Hz † | Triple Strike | |
Flashing 1Hz † | 2x Flash 2Hz | Triple Strike | |
Flashing 1.3Hz † | Flashing 2Hz † | Double Strike | |
Flashing 2Hz † | Triple Strike | Triple Strike | |
Double Strike | Steady High Power | Triple Strike | |
Triple Strike | Flashing 2Hz † | Double Strike | |
† Setting permitted for use as public mode fire alarm device |
Tone Table
Stage 1 | WAV file | Frequency Description. | Stage 2 | Stage 3 | Stage 4 |
---|---|---|---|---|---|
T 1 | ↓ | 1000 Continuous - PFEER Toxic Gas | T 3 | T 2 | T 44 |
T 2 | ↓ | 1200/500 @ 1Hz Sweeping - DIN / PFEER P.T.A.P. | T 1 | T 3 | T 44 |
T 3 | ↓ | 1000 @ 0.5Hz (1s on, 1s off) Intermittent - PFEER Gen. Alarm | T 1 | T 2 | T 44 |
T 4 | ↓ | 1.4KH-1.6KHz 1s, 1.6KHz-1.4KHz 0.5s - NF C 48-265 | T 44 | T 24 | T 1 |
T 5 | ↓ | 544(100mS)/440 (400mS) - NF S 32-001 | T 52 | T 19 | T 1 |
T 6 | ↓ | 1500/500 - (0.5s on , 0.5s off) x3 + 1s gap - AS4428 | T 7 | T 44 | T 1 |
T 7 | ↓ | 500-1500Hz Sweeping 2 sec on 1 sec off - AS4428 | T 6 | T 44 | T 1 |
T 8 | ↓ | 500/1200Hz @ 0.26Hz(3.3s on, 0.5s off) - NEN 2575 | T 44 | T 24 | T 35 |
T 9 | ↓ | 1000 (1s on, 1s off)x7 + (7s on, 1s off) - IMO Code 1a | T 18 | T 34 | T 1 |
T 10 | ↓ | 1000 (1s on, 1s off)x7 + (7s on, 1s off) - IMO Code 1a | T 21 | T 34 | T 1 |
T 11 | ↓ | 420(0.5s on, 0.5s off)x3 + 1s gap - ISO 8201 Temporal | T 44 | T 1 | T 8 |
T 12 | ↓ | 1000(0.5s on, 0.5s off)x3 + 1s gap - ISO 8201 Temporal | T 44 | T 1 | T 8 |
T 13 | ↓ | 422/775 - (0.85 on, 0.5 off) x3 + 1s gap - NFPA Temporal | T 44 | T 1 | T 8 |
T 14 | ↓ | 1000/2000 @ 1Hz - Singapore | T 23 | T 3 | T 35 |
T 15 | ↓ | 300 Continuous | T 44 | T 24 | T 35 |
T 16 | ↓ | 440 Continuous | T 44 | T 24 | T 35 |
T 17 | ↓ | 470 Continuous | T 44 | T 24 | T 35 |
T 18 | ↓ | 500 Continuous - IMO code 2 (Low) | T 44 | T 24 | T 35 |
T 19 | ↓ | 554 Continuous | T 64 | T 24 | T 35 |
T 20 | ↓ | 660 Continuous | T 44 | T 24 | T 35 |
T 21 | ↓ | 800 Continuous - IMO code 2 (High) | T 44 | T 24 | T 35 |
T 22 | ↓ | 1200 Continuous | T 44 | T 24 | T 35 |
T 23 | ↓ | 2000 Continuous | T 15 | T 3 | T 35 |
T 24 | ↓ | 2400 Continuous | T 48 | T 20 | T 35 |
T 25 | ↓ | 440 @ 0.83Hz (0.60s on, 0.60s off) Intermittent | T 1 | T 44 | T 8 |
T 26 | ↓ | 470 @ 0.9Hz (0.55s on, 0.55s off) Intermittent | T 1 | T 44 | T 8 |
T 27 | ↓ | 470 @ 5Hz (0.10s on, 0.10s off) Intermittent | T 1 | T 44 | T 8 |
T 28 | ↓ | 544 @ 1.14Hz (0.43s on, 0.44s off) Intermittent | T 44 | T 24 | T 8 |
T 29 | ↓ | 655 @ 0.875Hz (0.57s on, 0.57s off) Intermittent | T 1 | T 44 | T 8 |
T 30 | ↓ | 660 @ 0.28Hz (1.80s on, 1.80s off) Intermittent | T 44 | T 24 | T 8 |
T 31 | ↓ | 660 @ 3.3Hz (0.15s on, 0.15s off) Intermittent | T 30 | T 24 | T 8 |
T 32 | ↓ | 745 @ 1Hz (0.50s on, 0.50s off) Intermittent | T 44 | T 24 | T 8 |
T 33 | ↓ | 800 (0.25s on, 1.00s off) Intermittent | T 53 | T 24 | T 8 |
T 34 | ↓ | 800 @ 2Hz (0.25s on, 0.25s off) - IMO code 3.a (High) | T 56 | T 24 | T 8 |
T 35 | ↓ | 1000 @ 1Hz (0.50s on, 0.50s off) Intermittent | T 44 | T 24 | T 8 |
T 36 | ↓ | 2400 @ 1Hz (0.50s on, 0.50s off) Intermittent | T 21 | T 24 | T 8 |
T 37 | ↓ | 2900 @ 5Hz (0.10s on, 0.10s off) Intermittent | T 53 | T 24 | T 8 |
T 38 | ↓ | 363/518 @ 1Hz (0.50s / 0.50s) Alternating | T 1 | T 8 | T 19 |
T 39 | ↓ | 450/500 @ 2Hz (0.25s / 0.25s) Alternating | T 1 | T 8 | T 19 |
T 40 | ↓ | 554/440 @ 1Hz (0.50s / 0.50s) Alternating | T 44 | T 24 | T 19 |
T 41 | ↓ | 554/440 @ 0.65Hz (0.76s / 0.76s) Alternating | T 1 | T 8 | T 19 |
T 42 | ↓ | 561/760 @ 0.83Hz (0.60s / 0.60s) Alternating | T 1 | T 8 | T 19 |
T 43 | ↓ | 780/600 @ 0.96Hz (0.52s / 0.52s) Alternating | T 1 | T 8 | T 19 |
T 44 | ↓ | 800/1000 @ 2Hz (0.25s / 0.25s) Alternating | T 5 | T 24 | T 19 |
T 45 | ↓ | 970/800 @ 2Hz (0.25s / 0.25s) Alternating | T 1 | T 8 | T 19 |
T 46 | ↓ | 800/1000 @ 0.875Hz (0.57s / 0.57s) Alternating | T 53 | T 24 | T 19 |
T 47 | ↓ | 2400/2900 @ 2Hz (0.25s / 0.25s) Alternating | T 57 | T 24 | T 19 |
T 48 | ↓ | 500/1200 @ 0.3Hz (1.67s / 1.67s) Sweeping | T 44 | T 24 | T 12 |
T 49 | ↓ | 560/1055 @ 0.18Hz (2.73s / 2.73s) Sweeping | T 44 | T 24 | T 12 |
T 50 | ↓ | 560/1055 @ 3.3Hz (0.15s / 0.15s) Sweeping | T 44 | T 24 | T 12 |
T 51 | ↓ | 600/1250 @ 0.125Hz (4s / 4s) Sweeping | T 44 | T 24 | T 12 |
T 52 | ↓ | 660/1200 @ 1Hz (0.50s / 0.50s) Sweeping | T 64 | T 24 | T 12 |
T 53 | ↓ | 800/1000 @ 1Hz (0.50s / 0.50s) Sweeping | T 56 | T 24 | T 12 |
T 54 | ↓ | 800/1000 @ 7Hz (0.07s / 0.07s) Sweeping | T 57 | T 24 | T 12 |
T 55 | ↓ | 800/1000 @ 50Hz (0.01s / 0.01s) Sweeping | T 54 | T 24 | T 12 |
T 56 | ↓ | 2400/2900 @ 7Hz (0.07s / 0.07s) Sweeping | T 57 | T 24 | T 12 |
T 57 | ↓ | 2400/2900 @ 1Hz (0.50s / 0.50s) Sweeping | T 47 | T 24 | T 12 |
T 58 | ↓ | 2400/2900 @ 50Hz (0.01s / 0.01s) Sweeping | T 54 | T 24 | T 12 |
T 59 | ↓ | 2500/3000 @ 2Hz (0.25s / 0.25s) Sweeping | T 44 | T 24 | T 12 |
T 60 | ↓ | 2500/3000 @ 7.7Hz (0.65s / 0.65s) Sweeping | T 44 | T 24 | T 12 |
T 61 | ↓ | 800Hz Motor Siren | T 44 | T 24 | T 12 |
T 62 | ↓ | 1200Hz Motor Siren | T 44 | T 24 | T 12 |
T 63 | ↓ | 2400Hz Motor Siren | T 44 | T 24 | T 12 |
T 64 | ↓ | Simulated Bell | T 44 | T 21 | T 12 |
Country specific or custom tone configurations and alarm frequencies are available upon request. |